Model |
S-40-5 |
S-40-12 |
S-40-15 |
S-40-24 | |||
Output |
DC Voltage |
5V |
12V |
15V |
24V | ||
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% | |||
Rated Current |
8A |
3.5A |
2.8A |
1.8A | |||
Current Range |
0-8A |
0-3.5A |
0-2.8A |
0-1.8A | |||
Rated Power |
40W |
42W |
42W |
43W | |||
Ripple & Noise |
75mVp-p |
100mVp-p |
100mVp-p |
100mVp-p | |||
DC Voltage Adj. Range |
+10,-5% |
±10% |
±10% |
±10% | |||
Setup, Rise, Hold time |
800ms,50ms,15ms/115VAC 300ms,50ms,60ms/230VAC full load | ||||||
Input |
Voltage Range |
85~264 VAC 47~63 Hz;120~370VDC | |||||
AC Current |
1.2A/115 V 0.6A/ 230 V | ||||||
Efficiency |
72%/115VAC |
76%/115VAC |
76%/115VAC |
78%/115VAC | |||
Inrush Current |
Cold start 30A/115VAC 60A/230VAC | ||||||
Leakage Current |
<1 mA/240VAC | ||||||
Protection |
Over Load |
110%~160% | |||||
Protection type:current limiting,recovers automatically after fault condition is removed | |||||||
Over Voltage |
115%~135% | ||||||
Protection type:hiccup mode,recovers automatically after fault condition is removed | |||||||
Environment |
Working Temp. & Humidity |
-10℃~+60℃;20%~90 %RH | |||||
Storage Temp. & Humidity |
-20℃~+85℃;10%~95 %RH | ||||||
Vibration |
10~500Hz,2G 10min./1 cycle,period for 60min,each along X,Y,Z axes | ||||||
Safety |
Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||||
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | ||||||
Standards |
Safety Standard |
Design refer to UL1012, UL1950,TUV EN60950 | |||||
EMC Standard |
Design refer to EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,ENV50204,EN55024 | ||||||
Others |
Weight |
0.44Kg | |||||
Packing |
45pcs/20.3Kg/1.22CUFT | ||||||
Remarks |
1. All parameters not specially mentioned are measured at 230VAC input, rated load and 25℃of ambient temperature. 2. Ripple & Noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ&47μparallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equpment must be re-confirmed that it still meets EMC directives. 5. Concrete output current see Derating Curve. |